Model Number |
RS11V/LF-QPNHV |
Heating performance |
Min. |
Nominal |
Max. |
Heat output/Power consumption/COP at A7/W35℃ |
kW |
4.09/0.68/6.00 |
10.76/2.55/4.21 |
11.15/2.7/4.13 |
Heat output/Power consumption/COP at A2/W35℃ |
kW |
4.10/0.86/4.51 |
9.35/2.45/3.81 |
9.69/2.6/3.73 |
Heat output/Power consumption/COP at A-7/W35℃ |
kW |
2.87/1.34/2.13 |
8.15/2.55/3.20 |
8.45/2.69/3.14 |
Heat output/Power consumption/COP at A-10/W35℃ |
kW |
2.64/1.35/1.95 |
7.82/2.59/3.02 |
8.11/2.74/2.96 |
Heat output/Power consumption/COP at A-15/W35℃ |
kW |
2.16/1.28/1.67 |
6.20/2.63/2.36 |
6.43/2.78/2.31 |
Heat output/Power consumption/COP at A7/W45℃ |
kW |
3.75/1.00/3.75 |
11.77/3.33/3.54 |
12.20/3.52/3.47 |
Heat output/Power consumption/COP at A2/W45℃ |
kW |
4.19/1.47/2.85 |
8.73/2.95/2.96 |
9.05/3.12/2.90 |
Heat output/Power consumption/COP at A-7/W45℃ |
kW |
3.24/1.81/1.79 |
6.99/3.12/2.24 |
7.25/3.30/2.20 |
Heat output/Power consumption/COP at A-10/W45℃ |
kW |
3.04/1.81/1.68 |
6.38/3.17/2.01 |
6.61/3.36/1.97 |
Heat output/Power consumption/COP at A-15/W45℃ |
kW |
2.65/1.90/1.39 |
5.76/3.23/1.78 |
5.97/3.42/1.74 |
Heat output/Power consumption/COP at A7/W55℃ |
kW |
3.19/1.21/2.62 |
11.81/4.00/2.95 |
11.81/4.00/2.95 |
Cool output/Power consumption/EER at A35/W7℃ |
kW |
2.62/0.94/2.80 |
5.10/2.22/2.30 |
5.10/2.22/2.30 |
Nominal running current at A7/W35 outdoor /indoor unit |
A |
10.90 / 0.48 |
Aux. electric heater |
KW |
|
2.5 |
|
Max. power consumption outdoor/indoor unit |
KW |
4.00 / 2.62 |
Max. current outdoor/indoor unit |
A |
|
16.0 / 11.6 |
|
Power Supply |
|
220-240V/1phase/50Hz |
Compressor |
|
Panasonic EVI twin rotary |
Condenser |
|
Brazed plate heat exchanger |
Nominal flow heating medium |
m3/h |
1.85 |
Internal pressure drop at nominal flow |
kPa |
19 |
Nominal air flow |
m3/h |
3000 |
Nominal fan output |
W |
110 |
Max outlet heating medium temperature |
℃ |
55 |
Refrigerant R32 filling weight |
kg |
1.9 |
Dimensions outdoor unit (HxWxD) |
mm |
852 x 1065 x 446 |
Dimensions indoor unit (HxWxD) |
mm |
|
850 x 450 x 300 |
|
Pipe connector (water) |
|
G1' external thread |
gas pipe connector |
|
|
5/8" |
|
liquid pipe connector |
|
|
3/8" |
|
Net Weight |
kg |
80/32 |
Operating ambient temp. range |
℃ |
Heating -25~35 |
DHW -25~35 |
Cooling 10~43 |
Sound power level LWA |
dB(A) |
62 |
* the running current/power consumption in the bracket is the bivolent mode with aux. heater running |
|
The above data is tested by EN14511. A7/W35℃ means air temp. 7℃,outlet water temp. 35℃ |
|
The Sound power level is tested by EN12102 |
|
|
|
|